Re: [PATCH v2 1/2] sched/fair: Take thermal pressure into account while estimating energy

From: Lukasz Luba
Date: Thu Jun 10 2021 - 05:52:28 EST




On 6/10/21 10:41 AM, Vincent Guittot wrote:
On Thu, 10 Jun 2021 at 11:36, Lukasz Luba <lukasz.luba@xxxxxxx> wrote:



On 6/10/21 10:11 AM, Vincent Guittot wrote:
On Thu, 10 Jun 2021 at 10:42, Lukasz Luba <lukasz.luba@xxxxxxx> wrote:



On 6/10/21 8:59 AM, Vincent Guittot wrote:
On Fri, 4 Jun 2021 at 10:10, Lukasz Luba <lukasz.luba@xxxxxxx> wrote:

Energy Aware Scheduling (EAS) needs to be able to predict the frequency
requests made by the SchedUtil governor to properly estimate energy used
in the future. It has to take into account CPUs utilization and forecast
Performance Domain (PD) frequency. There is a corner case when the max
allowed frequency might be reduced due to thermal. SchedUtil is aware of
that reduced frequency, so it should be taken into account also in EAS
estimations.

SchedUtil, as a CPUFreq governor, knows the maximum allowed frequency of
a CPU, thanks to cpufreq_driver_resolve_freq() and internal clamping
to 'policy::max'. SchedUtil is responsible to respect that upper limit
while setting the frequency through CPUFreq drivers. This effective
frequency is stored internally in 'sugov_policy::next_freq' and EAS has
to predict that value.

In the existing code the raw value of arch_scale_cpu_capacity() is used
for clamping the returned CPU utilization from effective_cpu_util().
This patch fixes issue with too big single CPU utilization, by introducing
clamping to the allowed CPU capacity. The allowed CPU capacity is a CPU
capacity reduced by thermal pressure signal. We rely on this load avg
geometric series in similar way as other mechanisms in the scheduler.

Thanks to knowledge about allowed CPU capacity, we don't get too big value
for a single CPU utilization, which is then added to the util sum. The
util sum is used as a source of information for estimating whole PD energy.
To avoid wrong energy estimation in EAS (due to capped frequency), make
sure that the calculation of util sum is aware of allowed CPU capacity.

Signed-off-by: Lukasz Luba <lukasz.luba@xxxxxxx>
---
kernel/sched/fair.c | 17 ++++++++++++++---
1 file changed, 14 insertions(+), 3 deletions(-)

diff --git a/kernel/sched/fair.c b/kernel/sched/fair.c
index 161b92aa1c79..1aeddecabc20 100644
--- a/kernel/sched/fair.c
+++ b/kernel/sched/fair.c
@@ -6527,6 +6527,7 @@ compute_energy(struct task_struct *p, int dst_cpu, struct perf_domain *pd)
struct cpumask *pd_mask = perf_domain_span(pd);
unsigned long cpu_cap = arch_scale_cpu_capacity(cpumask_first(pd_mask));
unsigned long max_util = 0, sum_util = 0;
+ unsigned long _cpu_cap = cpu_cap;
int cpu;

/*
@@ -6558,14 +6559,24 @@ compute_energy(struct task_struct *p, int dst_cpu, struct perf_domain *pd)
cpu_util_next(cpu, p, -1) + task_util_est(p);
}

+ /*
+ * Take the thermal pressure from non-idle CPUs. They have
+ * most up-to-date information. For idle CPUs thermal pressure
+ * signal is not updated so often.

What do you mean by "not updated so often" ? Do you have a value ?

Thermal pressure is updated at the same rate as other PELT values of
an idle CPU. Why is it a problem there ?



For idle CPU the value is updated 'remotely' by some other CPU
running nohz_idle_balance(). That goes into
update_blocked_averages() if the flags and checks are OK inside
update_nohz_stats(). Sometimes this is not called
because other_have_blocked() returned false. It can happen for a long

So i miss that you were in a loop and the below was called for each
cpu and _cpu_cap was overwritten

+ if (!idle_cpu(cpu))
+ _cpu_cap = cpu_cap - thermal_load_avg(cpu_rq(cpu));

But that also means that if the 1st cpus of the pd are idle, they will
use original capacity whereas the other ones will remove the thermal
pressure. Isn't this a problem ? You don't use the same capacity for
all cpus in the performance domain regarding the thermal pressure?

True, but in the experiments for idle CPUs I haven't
observed that they still have some big util (bigger than _cpu_cap).
It decayed already, so it's not a problem for idle CPUs.

But it's a problem because there is a random behavior : some idle cpu
will use original capacity whereas others will use the capped value
set by non idle CPUs. You must have consistent behavior across all
idle cpus.

Then, if it's not a problem why adding the if (!idle_cpu(cpu))

To capture the signal value from a running CPU, which then I pass
into the em_cpu_energy() in path 2/2. My apologies for confusion,
this can be just local variable for patch 1/2.

I can create the _cpu_cap as local variable inside this loop,
just for this patch. Then in patch 2/2 I will remove it and define
above the loop, to be available for the call to
em_cpu_energy().