Re: [PATCH v3 3/3] Documentation: hwmon: Document the IBM CFF power supply
From: Guenter Roeck
Date: Mon Aug 14 2017 - 14:53:19 EST
On Mon, Aug 14, 2017 at 10:26:30AM -0500, Eddie James wrote:
> From: "Edward A. James" <eajames@xxxxxxxxxx>
>
> Signed-off-by: Edward A. James <eajames@xxxxxxxxxx>
> ---
> Documentation/hwmon/ibm-cffps | 54 +++++++++++++++++++++++++++++++++++++++++++
> 1 file changed, 54 insertions(+)
> create mode 100644 Documentation/hwmon/ibm-cffps
>
> diff --git a/Documentation/hwmon/ibm-cffps b/Documentation/hwmon/ibm-cffps
> new file mode 100644
> index 0000000..e091ff2
> --- /dev/null
> +++ b/Documentation/hwmon/ibm-cffps
> @@ -0,0 +1,54 @@
> +Kernel driver ibm-cffps
> +=======================
> +
> +Supported chips:
> + * IBM Common Form Factor power supply
> +
> +Author: Eddie James <eajames@xxxxxxxxxx>
> +
> +Description
> +-----------
> +
> +This driver supports IBM Common Form Factor (CFF) power supplies. This driver
> +is a client to the core PMBus driver.
> +
> +Usage Notes
> +-----------
> +
> +This driver does not auto-detect devices. You will have to instantiate the
> +devices explicitly. Please see Documentation/i2c/instantiating-devices for
> +details.
> +
> +Sysfs entries
> +-------------
> +
> +The following attributes are supported:
> +
> +curr1_alarm Output current over-current fault.
> +curr1_input Measured output current in mA.
> +curr1_label "iout1"
> +
> +fan1_alarm Fan 1 warning.
> +fan1_fault Fan 1 fault.
> +fan1_input Fan 1 speed in RPM.
> +fan2_alarm Fan 2 warning.
> +fan2_fault Fan 2 fault.
> +fan2_input Fan 2 speed in RPM.
> +
> +in1_alarm Input voltage under-voltage fault.
Just noticed. Are you sure you mean 'fault' here and below ?
'alarm' attributes normally report an over- or under- condition,
but not a fault. Faults should be reported with 'fault' attributes.
In PMBus lingo (which doesn't distinguish a real 'fault' from
a critical over- or under- condition), the "FAULT" condition
usually maps with the 'crit_alarm' or 'lcrit_alarm' attributes.
Also, under-voltages would normally be reported as min_alarm
or clrit_alarm, not in_alarm.
> +in1_input Measured input voltage in mV.
> +in1_label "vin"
> +in2_alarm Output voltage over-voltage fault.
> +in2_input Measured output voltage in mV.
> +in2_label "vout1"
> +
> +power1_alarm Input fault.
Another example; this maps to PMBUS_PIN_OP_WARN_LIMIT which is an
input power alarm, not an indication of a fault condition.
> +power1_input Measured input power in uW.
> +power1_label "pin"
> +
> +temp1_alarm PSU inlet ambient temperature over-temperature fault.
> +temp1_input Measured PSU inlet ambient temp in millidegrees C.
> +temp2_alarm Secondary rectifier temp over-temperature fault.
Interestingly, PMBus does not distinguish between a critical temperature
alarm and an actual "fault". Makes me wonder if the IBM PS reports
CFFPS_MFR_THERMAL_FAULT if there is an actual fault (chip or sensor failure),
or if it has the same meaning as PB_TEMP_OT_FAULT, ie an excessively high
temperature.
If it is a real fault (a detected sensor failure), we should possibly
consider adding a respective "virtual" temperature status flag. The same
is true for other status bits reported in the manufacturer status
register if any of those reflect a "real" fault, ie a chip failure.
> +temp2_input Measured secondary rectifier temp in millidegrees C.
> +temp3_alarm ORing FET temperature over-temperature fault.
> +temp3_input Measured ORing FET temperature in millidegrees C.
> --
> 1.8.3.1
>