On Tue, 30 Jun 2020, Ming Lei wrote:
> On Wed, Jun 24, 2020 at 5:01 AM Henrique de Moraes Holschuh
> <hmh@xxxxxxxxxx> wrote:
> > Cache flushes do not matter that much when SSDs and sudden power cuts
> > are involved. Power cuts at the wrong time harm the FLASH itself, it is
> > not about still-in-flight data.
> >
> > Keep in mind that SSDs do a _lot_ of background writing, and power cuts
>
> What is the __lot__ of SSD's BG writing? GC?
GC, and scrubbing.
> > during a FLASH write or erase can cause from weakened cells, to much
> > larger damage. It is possible to harden the chip or the design against
> > this, but it is *expensive*. And even if warded off by hardening and no
> > FLASH damage happens, an erase/program cycle must be done on the whole
> > erase block to clean up the incomplete program cycle.
>
> It should have been SSD's(including FW) responsibility to avoid data loss when
> the SSD is doing its own BG writing, because power cut can happen any time
> from SSD's viewpoint.
Oh, I fully agree. And yet, we had devices from several large vendors
complaining about unclean shutdowns. So, "it should have been", as
usual, amounts to very little in the end.
> > When you do not follow these rules, well, excellent datacenter-class
> > SSDs have super-capacitor power banks that actually work. Most SSDs do
> > not, although they hopefully came a long way and hopefully modern SSDs
> > are not as easily to brick as they were reported to be three or four
> > years ago.
>
> I remember that DC SSDs often don't support BG GC.
And have proper supercap local power banks, etc. I'd say they're not
really relevant to this thread.
--
Henrique Holschuh