Re: pmbus: dealing with unsigned mantissa in linear reading
From: Guenter Roeck
Date: Tue Jun 15 2021 - 21:46:27 EST
On Tue, Jun 15, 2021 at 11:34:53PM +0000, Chris Packham wrote:
> Hi Guenter,
>
> I've had a report from someone testing the BPA-RS600.
>
> When they have the input voltage set to >= 256V (apparently the PSU can
> handle input up to 264V). The Vin reading goes negative.
>
> CMD 0x88, VAL=0xf3f8, Vin=254
> CMD 0x88, VAL=0xf3fc, Vin=255
> CMD 0x88, VAL=0xf400, Vin=-256
>
> Looking at pmbus_reg2data_linear() the mantissa is cast to s16 which is
> correct according to section 7.1 of the PMBUS spec which says that the
> mantissa is an 11-bit two's complement value.
>
> It seems that the BPA-RS600 is using a non-standard format for the
> mantissa (probably because the range of the standard linear encoding
> can't support values >255V). Does the pmbus infrastructure provide a way
> for me to define a custom format/conversion for a given sensor?
Essentially you'll have to implement a custom read word function and
convert the value reported by the power supply to a valid linear11
value. In this case, you may have to shift the reported value by 1 bit
and increase the exponent by one.
Not sure what you mean with "standard linear encoding can't support values
>255V". Why not ? That is what the exponent is for, after all. It rather
seems to me that the PS vendor decided to violate the standard to get
another bit of accuracy.
Guenter