On Tue, Dec 07, 2021 at 11:44:01AM PST, Guenter Roeck wrote:
On 12/7/21 11:22 AM, Zev Weiss wrote:
On Tue, Dec 07, 2021 at 09:50:15AM PST, Guenter Roeck wrote:
On Mon, Dec 06, 2021 at 11:15:20PM -0800, Zev Weiss wrote:
This device is an integrated module of the Delta AHE-50DC Open19 power
shelf. For lack of proper documentation, this driver has been developed
referencing an existing (GPL) driver that was included in a code release
from LinkedIn [1]. It provides four fan speeds, four temperatures, and
one voltage reading, as well as a handful of warning and fault
indicators.
[1] https://github.com/linkedin/o19-bmc-firmware/blob/master/meta-openbmc/meta-linkedin/meta-deltapower/recipes-kernel/fancontrol-mod/files/fancontrol.c
Hmm, that reference isn't really accurate anymore. I think it would be
better to just say that the device was found to be PMBus compliant.
Sure, will do.
Makes me wonder: How do you know that the referenced driver is for Delta AHE-50DC ?
We'd been waiting for the source code for the software it ships with for a while, and were finally provided with that repo; everything I've observed from the factory software is consistent with the code in that driver. A sampling:
Can you check this with real hardware, by any chance ?
If you mean running that code on it, yes -- here's the userspace utility that invokes that library routine:
root@bmc-oob:~# fan-util.sh
fan1 speed: 7860 RPM
fan2 speed: 7860 RPM
fan3 speed: 7620 RPM
fan4 speed: 7560 RPM
temperature1: 29.20 C
temperature2: 27.80 C
temperature3: 28.50 C
temperature4: 30.20 C
vin_undervolt_fault: no
overtemperature_warning: no
fan_fault: no
fan_warning: no
fan_status: ok